Amprobe AMP-330 1000A AC-DC TRMS Motor Maintenance Clamp Meter
Advanced AC DC Measurement for Professional Electrical Testing
Amprobe AMP-330 AC-DC TRMS Clamp Meter is a professional electrical testing instrument designed for electricians, engineers, and maintenance technicians, making the Amprobe AMP-330 1000A AC-DC TRMS Clamp Meter Price in Bangladesh a relevant search for dependable measurement equipment. Its versatile clamp design and true RMS technology provide practical support for current measurement, electrical inspection, troubleshooting, and maintenance applications.
The AMP-330 is designed to support both AC and DC current measurement, making it a versatile tool for professionals working with different types of electrical systems. This capability allows technicians to evaluate circuit conditions, inspect equipment performance, and troubleshoot electrical faults using a single practical instrument.
True RMS technology helps provide reliable readings when testing electrical systems with distorted or complex waveforms. This is particularly useful when working with modern electrical equipment, variable loads, and electronic systems where conventional measurement methods may not provide the same level of confidence.
The clamp mechanism allows users to measure current without disconnecting the conductor from the circuit. This non invasive approach helps minimize circuit interruption and makes testing more efficient. It is especially useful for inspecting installed equipment, electrical panels, distribution systems, and machinery.
Reliable electrical measurements are essential for identifying faults and evaluating system performance. The Amprobe AMP-330 can assist technicians in investigating abnormal current conditions, checking equipment operation, and supporting systematic troubleshooting. Its versatile measurement capability makes it suitable for both routine diagnostics and detailed service work.
The AMP-330 is suitable for a wide range of electrical testing applications. Electricians can use it during installation and maintenance, while engineers and service technicians can apply it for equipment diagnostics and preventive inspection. Its combination of AC and DC measurement capability makes it a useful instrument for diverse electrical environments.
The clamp meter format provides convenient access to electrical conductors while helping technicians work efficiently around installed equipment. Its practical design is suitable for workshop testing, commercial facilities, industrial environments, and on site service applications. Portability also makes it convenient for professionals who regularly move between different work locations.
The AMP-330 is designed to simplify routine electrical testing. Its clamp based operation reduces the need for direct conductor contact, while its digital measurement system allows users to monitor readings clearly. These features can help improve workflow during repeated inspections, troubleshooting procedures, and maintenance activities.
Designed for demanding electrical testing environments, the Amprobe AMP-330 offers a professional construction suitable for regular use. Proper handling and storage can help maintain reliable performance over time. Its practical design makes it a useful addition to the toolkit of technicians who require dependable equipment for ongoing field and workshop work.
The Amprobe AMP-330 is a practical choice for professionals seeking a versatile AC DC TRMS clamp meter for electrical measurement and troubleshooting. Its true RMS technology, convenient clamp operation, broad measurement capability, and professional design make it a valuable testing instrument for electricians, engineers, maintenance professionals, and service technicians. It provides a practical solution for efficient electrical inspection and diagnostic work.
| FEATURE | AMP-210 | AMP-220 | AMP-310 | AMP-320 | AMP-330 | |
| AC voltage (True-rms) | Range: | 0 to 600.0 V | 0 to 1000.0 V | |||
| Accuracy: | ±1.0% + 5LSD (50 to 60 Hz) | ±0.8% + 5LSD (50 to 60 Hz) | ||||
| DC voltage | Range: | 0 to 600.0 V | ||||
| Accuracy: | ±1.0% + 5LSD | |||||
| AC+DC voltage | Range: | – | 0 to 600.0 V | – | 0 to 600.0 V | 0 to 1000.0 V |
| Accuracy: | – | ±1.2% + 7LSD (50 to 60 Hz) | – | ±1.2% + 7LSD (50 to 60 Hz) | ±1.0% + 7LSD (50 to 60 Hz) ±1.8% + 7LSD (DC 40 to 200 Hz) ±1.2% + 7LSD 200 to 400 Hz) |
|
| AC current | Range: | 0 to 600.0 A | ||||
| Accuracy: | ±1.8% + 5LSD (50 to 60 Hz) ±2.0% + 5LSD (100 to 400 Hz) |
|||||
| DC current | Range: | – | 0 to 600.0 A | – | 0 to 600.0 A | 0 to 1000.0 A |
| Accuracy: | – | ±2.0% + 5LSD (DC 50 to 100 Hz) | – | ±2.0% + 5LSD (DC 50 to 100 Hz) | ±1.8% + 5LSD (DC 50 to 100 Hz) | |
| AC+DC current | Range: | – | 0 to 600.0 A | – | 0 to 600.0 A | 0 to 1000.0 A |
| Accuracy: | – | ±2.2% + 7LSD (DC 50 to 100 Hz) ±2.7% + 7LSD (100 to 400 Hz) |
– | ±2.2% + 7LSD (DC 50 to 100 Hz) ±2.7% + 7LSD (100 to 400 Hz) |
±2.2% + 7LSD (40 to 100 Hz) ±2.5% + 7LSD (100 to 400 Hz) |
|
| Precise low current AC | Range: | 0 to 60.00 A | ||||
| Accuracy: | ±1.5% + 5LSD (50 to 60 Hz) | ±1.5% + 5LSD (50 to 60 Hz) ±2.0% + 5LSD (0.00 to 20.00 A, 100 to 400 Hz) ±3.0% + 5LSD (>20.00 to 60.00 A, 40 to 100 Hz) ±3.0% + 5LSD (>20.00 to 60.00 A, 100 to 100 Hz) |
||||
| Precise low current DC | Range: | – | 0 to 60.0 A | – | 0 to 60.0 A | 0 to 60.00 A |
| Accuracy: | – | ±2.0% + 5LSD | – | ±2.0% + 5LSD | ±1.5% + 5LSD (0.00 to 20.00 A) ±3.0% + 5LSD (>20.00 to 60.00 A) |
|
| Micro amps | Range: | – | – | 0 to 2000 µA | ||
| Accuracy: | – | – | ±1.0% + 5LSD | |||
| Frequency | Range: | 5.00 to 999.9 Hz | ||||
| Accuracy: | ±1.0% + 5LSD (600 V range) | |||||
| Range: | 50.0 to 400.0 Hz | |||||
| Accuracy: | ±2.0% + 4LSD (600 A range) | |||||
| Resistance | Range: | 0.0 to 60.00 kΩ | ||||
| Accuracy: | ±1.0% + 5LSD | |||||
| Capacitance | Range: | 0.0 to 2500 µF | ||||
| Accuracy: | ±2.0% + 4LSD | |||||
| Continuity beeper | ON ≤ 10 Ω | |||||
| Off > 250 Ω | ||||||
| Temperature* (Type K thermocouple) |
– | – | -40.0 to 752 °F -40.0 to 400 °C |
|||
| – | – | ±1.0% + 3.0 °F (-40.0 to 14.0 °F) ±1.0% + 1.5 °F (>40.0 to 99.9 °F) ±1.0% + 2.0 °F (100 to 752 °F) ±1.0% + 1.5 °C (-40.0 to 10.0 °C) ±1.0% + 0.8 °C (>-10.0 to 99.9 °C) ±1.0% + 1.0 °C (100 to 400 °C) |
||||
| Non-contact voltage | 10 V to 1000 V AC (50 to 60 Hz) | |||||
| Phase rotation indication | – | – | Rotation-R for main supply Rotation-M for motors |
|||
| Diode test | • | • | • | • | • | |
| Jaw opening | 1.18 in (30 mm) | 1.37 in (35 mm) | 1.18 in (30 mm) | 1.37 in (35 mm) | 2.0 in (51 mm) | |
| Safety rating | CAT III 600 V | CAT IV 600V CAT III 1000 V |
||||
| Special Features | ||||||
| In-rush current | – | • | &b | |||
No resources available for this product.
No reviews yet. Be the first to review this product!